Memorias de investigación
Artículos en revistas:
ESTIMATION OF VOLTAGE SAGS FROM A LIMITED SET OF MONITORS IN POWER SYSTEMS
Año:2017

Áreas de investigación
  • Ingeniería eléctrica,
  • Gestión técnica de los sistemas de energía eléctrica

Datos
Descripción
This paper proposes a probabilistic method aimed at estimating the voltage sag frequency of nonmonitored sites given the number of sags recorded by a limited set of voltage sag monitors. The proposed method is based on simulating a representative database of feasible pseudomeasurements by using probabilistic values of fault coefficient, fault impedance, fault type, and fault location. This information is processed through Bayesian filtering based on the Bayes' probabilistic theorem. This enables obtaining the most probable voltage sag index at nonmonitored busbars given the index measured at monitored busbars. This statistical estimation of sag indices at locations where there are no monitors constitutes the main contribution of this paper. This study is developed in three power systems: the IEEE 24-busbar reliability test system, the IEEE 118-busbar test system, and the transmission network of Ecuador with 357 busbars.
Internacional
Si
JCR del ISI
Si
Título de la revista
Ieee Transactions on Power Delivery
ISSN
0885-8977
Factor de impacto JCR
2,032
Información de impacto
Datos JCR del año 2015
Volumen
32
DOI
10.1109/TPWRD.2016.2594232
Número de revista
2
Desde la página
656
Hasta la página
665
Mes
ABRIL
Ranking

Esta actividad pertenece a memorias de investigación

Participantes

Grupos de investigación, Departamentos, Centros e Institutos de I+D+i relacionados
  • Creador: Departamento: Automática, Ingeniería Eléctrica y Electrónica e Informática Industrial