Descripción
|
|
---|---|
This paper discusses problems that can occur in synchronous generators during the paralleling connection process when connecting them to an electric network. Faulty or inadequate synchronization causes over-currents and high electromagnetic torque values that can damage generators. Moreover, it can cause power oscillations in the electric network that could collapse the system. Despite this risk, conventional synchronous generator protection systems do not trip specifically during faulty synchronization. A new protection method, based on an instantaneous overcurrent protection for electric generators during faulty synchronization incidents, is presented in this paper. The method is verified by computer simulations of a thermal power plant turbo alternator. | |
Internacional
|
Si |
Nombre congreso
|
2018 XIII International Conference on Electrical Machines (ICEM) |
Tipo de participación
|
960 |
Lugar del congreso
|
Alexandroupoli, Greece |
Revisores
|
Si |
ISBN o ISSN
|
978-1-5386-2477-7 |
DOI
|
10.1109/ICELMACH.2018.8507024 |
Fecha inicio congreso
|
03/09/2018 |
Fecha fin congreso
|
06/09/2018 |
Desde la página
|
2385 |
Hasta la página
|
2390 |
Título de las actas
|
Protection Method for Synchronous Machine During the Paralleling Connection Process |