Memorias de investigación
Ponencias en congresos:
Improvement of the Ground-Fault Detection in Field Windings of Synchronous Machines with Static Excitation based on Third-Harmonic Voltage Phase-Angle Comparison
Año:2015

Áreas de investigación
  • Ingeniería eléctrica, electrónica y automática

Datos
Descripción
This paper presents the theoretical approach and experimental tests of a new algorithm for detecting ground faults in rotor windings of synchronous generators with static excitation. This location method requires the installation of a grounding resistance in the secondary winding of the excitation transformer. First, the third-harmonic reference voltage is obtained by the voltage measurements in the excitation system. Then, the third-harmonic voltage at the grounding resistor is compared to the reference voltage. The ground fault is detected when the phase angle between those voltages is under the trip setting value. This new algorithm has been tested in a 5 kVA Synchronous generator with satisfactory results.
Internacional
Si
Nombre congreso
Power Electronics and Applications (EPE'15 ECCE-Europe), 2015 17th European Conference on
Tipo de participación
960
Lugar del congreso
GENEVA
Revisores
Si
ISBN o ISSN
978-1-4799-7743-7
DOI
10.1109/EPE.2015.7311685
Fecha inicio congreso
08/09/2015
Fecha fin congreso
10/09/2015
Desde la página
1
Hasta la página
9
Título de las actas
Power Electronics and Applications (EPE'15 ECCE-Europe), 2015 17th European Conference on

Esta actividad pertenece a memorias de investigación

Participantes

Grupos de investigación, Departamentos, Centros e Institutos de I+D+i relacionados
  • Creador: Grupo de Investigación: Generación eléctrica con energía eólica
  • Departamento: Automática, Ingeniería Eléctrica y Electrónica e Informática Industrial